Share:
PRODUCTS
CYECVT1-36N Electronic Combined Current and Voltage Transformer

The products have designed base on IEC60044-8, GB/T20840.8-2007&IEC60044-7,GB/T20840.7-2007 standards, and customers special design service. This series are utilized LPCT&Rogowski coil to meter current in circle, conduct Resistor divider to measure voltage. Installed in any switchgear with High tense voltage below 10kV, compatible with electric instrument, digital measure and protective equipment, able to conduct multifunction such as measure, control, protection and data transmission etc simultaneity.

DESCRIPTION

Main technical parameter

1Rated primary voltage : 35/√3kV
2
Rated primary current : 50-1500A
3
Rated secondary output :
   ECT
:  4V (measure),  200mV (protection )
   EVT
: 3.5/√3V, 3.25/√3V  or  6.5/√3V

4. Rated Burden: >10kΩ(ECT). >1MΩ(EVT)
5
Rated digital output : 0x2D41( measure)0x01CF(protection)
6
Accuracy for measure winding : 0.2(ECT) ,0.2(EVT)
7
Accuracy for protection winding : 5TPE(ECT)3P(EVT)
8
Rated frequency : 50Hz
9
Rated insulation level : 40.5/95/200kV
10
Rated short time thermal current : 50-200: 150Ipr, 300-1500A :31.5kA/1S
11
Rated dynamic current : 50-200A :375Ipr, 300-1500A :80kA
12
Ambient temperature : -5℃-40℃(indoor)
13
Ambient humidity : ≤RH95%(25℃)
14
Altitude : ≤ 2000m (custom design)
15
Installation site : indoor

Outline drawing


Contact Us

Calls:

Switchboard:0086-755-86000443

International Sales :0086-755-860007、00861313823790397

international2@chuangy.com

Room 101 / 401, Building B, Jiada R&D Building, Songpingshan Road No.5, Songpingshan Community, Xili Street, Nanshan District, Shenzhen, China


China Southern:0086-756-3639005、008613923479219

cyty@chuangy.com

No.24, Keji 5th Road, Tangjiawan Town, High-tech Zone, Zhuhai, China


China Eastern:0086-792-6893555、008613767272953

sales6@chuangy.com

No.31 Lushandong Road, Shacheng Industrial Park, Jiujiang County, Jiangxi Province, China



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号