OMA-17.5F,OMA-24F,OMA-36F
Overhead pole mounted primary metering unit
1. Basic parameters:
|
No.
|
item
|
units
|
specification
|
|
1.
|
Highest voltage for
equipment Um (r.m.s.)
|
kV
|
17.5
|
24
|
36
|
|
2.
|
rated frequency (fR)
|
Hz
|
50, 60 or 50/60
|
|
3.
|
Rated lightning impulse
withstand voltage (peak)
|
kV
|
95kV,110 kV
|
125 kV,150 kV
|
170 kV,200 kV
|
|
4.
|
Rated power-frequency
withstand voltage on primary
|
kV
|
38
|
50
|
70
|
|
5.
|
Rated power-frequency
withstand voltage on secondary
|
kV
|
3
|
|
6.
|
Number of CTs and VTs
|
pcs
|
3VT+3CT
|
|
7.
|
Standard
|
/
|
IEC 61869-1:2007、 IEC 61869-2:2012
IEC 61869-3:2011、IEC 61869-4:2013
IEEE C57.13-2016
|
2. Product function and use:
Overhead pole mounted primary metering unit complies with the latest applicable industry standards and local and/or national electrical regulations (IEC, IEEE (ANSI), CAN, GOST, CEF). Used for three-phase overhead power grid energy metering management, distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce the loss.
3. Main features of the product:
1. The medium voltage transformer of the metering unit is composed of 3 single-phase combined transformers, which saves installation space. It is convenient and quick to install directly on the pole outdoors.
2. The metering unit is equipped with a junction box that has installed the test terminal block and the lead wire connected to the transformer. The junction box door lock seal structure is designed to prevent electricity theft. At the same time, it can also be equipped with an electric meter box on the column.
3. The meter box body is made of stainless steel or corrosion-resistant low-carbon steel with the same performance, and the sealing design is weatherproof. The surface is coated with anticorrosive paint powder layer, which is resistant to acid and alkali corrosion and UV.
4. The medium voltage combined transformer is insulated with epoxy resin solid encapsulation, and the surface is dirt-resistant and UV-resistant. It has excellent dielectric and mechanical properties, no oil, no gas, no maintenance. It can meet the requirements of safe operation and environmental protection.
5. The CT of the medium voltage combined transformer can be configured with dual ratios. VT can choose anti-short circuit and overload protection design to avoid burning and explosion caused by VT short circuit and overload.
6. One connection uses NEMA contact bar and wiring clamp connection. The terminal block of the corresponding area can be configured according to user requirements, and the lightning arrester can be selected as required.
4. Product technical parameters:
Current transformer specifications
|
No
|
Item
|
规格参数
|
|
1.
|
Rated primary current
|
5A up to 1200A
|
|
2.
|
Rated secondary current
|
5A或1A
|
|
3.
|
Rated Continuous Thermal Current
|
120%,125%,150%,200%,etc.
|
|
4.
|
Rated Short time current (Ith) (thermal 1 second)
|
80xIpr,100xIpr
|
|
5.
|
Rated Dynamic Current (Idyn)
|
2.5xIth
|
|
6.
|
Rated Output(VA)
|
5,10,12.5,15,20
|
|
7.
|
Accuracy Class
|
0.2S,0.2,0.5S,0.5,1 Metering
|
|
8.
|
Instrument Security Factor (FS)
|
5,10,20
|
|
9.
|
Applicable Standard
|
IEC: 61869-1&2
|
Voltage transformer specifications
|
No
|
Item
|
规格参数
|
|
1.
|
Rated primary voltage(V)
|
13200/√3,
13800/√3,
8400, etc.
|
20000/√3,
22000/√3,
14400, etc.
|
33000/√3,35000/√3,
20125, etc.
|
|
2.
|
Rated secondary voltage(V)
|
100/√3,110/√3, 115/√3, 120/√3, 110,115,120
|
|
3.
|
Rated Voltage Factor
|
1.2/Continuous
1.5/30s,1.9/30s,1.9/8h
1.5/30s,1.9/30s,1.9/8h
|
|
4.
|
Standard connection
|
Y-Y connection
|
|
5.
|
Rated Output(VA)
|
15,20,25,30,50,75
|
|
6.
|
Accuracy Class
|
0.2,0.5,1,3 Metering
|
|
7.
|
Thermal burden(VA)
|
500
|
500
|
750
|
|
8.
|
Applicable Standard
|
IEC: 61869-1&3
|
If the parameters required by the user exceed the range of the above table, it can be determined after consultation with our company。
5. Product dimensions and wiring schematic diagram:
OMA-17.5F、OMA-24F Apearance Dimension Drawing
OMA-36F Apearance Dimension Drawing
Optional meter box 1 (IEC) size can be made as required、
Optional meter box 2 (ANSI) size can be made as required
Wiring Diagram
6. Special requirement
Other specifications are available as per clients’ requests.