Share:
PRODUCTS
JDZXR-12C VOLTAGE TRANSFORMER

JDZXR-12C

VOLTAGE TRANSFORMER

□  12kV Indoor Single-Phase Epoxy Resin Type


Epoxy resin casting and full enclosed construction, is used indoor

switch cabinet to measure the  , electric energy and protective

relaying in single phase or three phase AC circuit with the frequency

50Hz or 60Hz and highest voltage for equipment 12 kV.

The iron core adopts advanced cold-rolled silicon steel sheet. High

voltage outgoing line of primary winding was fetched out from top of

the product; outgoing line of secondary winding was fetched out from

transverse side of the product.

Technical Data

1、Installation site      indoor

2、Rated frequency        50/60Hz

3、Load power factor:      cosΦ=0.8 (lagging)

4、Technical standard accords with    IEC 60044-2

(IEC 61869-1&3)

DESCRIPTION

Specification

Type

Rated primary

voltage (kV)

Rated secondary voltage (kV)

Accuracy classes combination

Rated output

 (VA)

Thermal limiting current

(VA)

Rated insulation level(kV)

JDZXR-12C

11/√3

0.11/√3

0.2

15

400

12/28/75

0.5

30

1

80

0.11/√3/0.11/3

0.2/6P

15/50

300

0.5/6P

30/50


Outline



Contact Us

Calls:

Switchboard:0086-755-86000443

International Sales :0086-755-860007、00861313823790397

international2@chuangy.com

Room 101 / 401, Building B, Jiada R&D Building, Songpingshan Road No.5, Songpingshan Community, Xili Street, Nanshan District, Shenzhen, China


China Southern:0086-756-3639005、008613923479219

cyty@chuangy.com

No.24, Keji 5th Road, Tangjiawan Town, High-tech Zone, Zhuhai, China


China Eastern:0086-792-6893555、008613767272953

sales6@chuangy.com

No.31 Lushandong Road, Shacheng Industrial Park, Jiujiang County, Jiangxi Province, China



Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号