Technical data:
|
Model
|
CY-RAM2000
|
|
Current range
|
2000A
|
|
Accuracy
|
±1%(5%~120%In) @45-65Hz
|
|
Linearity
|
±0.3% (5%~120%In)
|
|
Position sensitivity
|
±2%
|
|
External influence
|
±1% range (distance to coil >200mm)
|
|
Temperature coefficient
|
± 0.08 % /℃ of the reading data
|
|
Frequency range
|
10 Hz to 20 kHz (-3dB)
|
|
Power supply
|
4*AA| MN1500|LR6 battery
(external adapter 9~12V DC)
|
|
Overload indication
|
过载超量程120%时指示(显示Alarm)
Indicate when overload over 120%, (display Alarm)
|
|
Automatic shutdown time
|
15 min@ No current acquisition signal
|
|
Operating Voltage
|
600 V AC RMS
|
|
Cable length
|
2 meters,(measuring probe to the electronics module)
|
|
Weight
|
250 g(measuring probe ),160 g( electronics module)
|
Dimension and Schematic: Unit:mm
Component name
①flexible rogowski coil A
②flexible rogowski coil B
③current measuring input terminal A
④current measuring input terminal B
⑤LCD(liquid crystal display)
⑥B/L button, Backlight switch
⑦Hold button (debug button)
⑧Power button
⑨Battery compartment rear cover
Button function:
⑧Power button: switch key, long press more than 3 seconds turn on/off;
⑦Hold button : data hold key, short press to keep the current data, press again to return to normal;
⑥B/L button: short press to turn on or off the LCD backlight, long press debug two channels for the same value.
Usage instruction:
Attention:
1. To achieve best accuracy, flexible rogowski coil measurement probe should keep consistent with A, B channel when connection.
2. When the display shows low power, display dim, can not boot, you should replace the battery.
3 When the display is not normal (e.g. only two lines are displayed), remove the battery and reload it.