Share:
PRODUCTS
Locatin : Products > Instrument Transformers > MV & LV CT PT > Outdoor CT/PT
JLSZXW1-36 OUTDOOR COMBINED TRANSFORMER
OUTDOOR COMBINED TRANSFORMER JLSZXW1-36

This three phase combined CT&VT consists of three semi-insulation VTs and three CTs. VT connected with CT terminal P1, CT series connected with phase A(B,C), secondary leads in junction box is easy for wiring and testing. Use epoxy resin insulation stunt structure for outdoor installation. Applicable for highest voltage for equipments no more than 40.5kV for current/voltage measurement in power system.

Technical Data:
1.Installation site: outdoor
2.Rated Frequency: 50/60Hz
3.Burden power factor: Cosφ=0.8(lagging)

4.Technical standard accords with IEC 60044-1&2,IEC 61869-1 & 2 & 3



DESCRIPTION

Main technical parameter:

Rated frequency: 50/60Hz: 
Rated insulation level: 36/70/170kV (IEC) or 40.55/95/200kV (GB)

Voltage Ratio

(kV)

Accuracy Class

Rated Burden (VA)

Current Ratio

(A)

Accuracy Class

Rated Burden

(VA)

66000/√3/0.12

66000/√3/0.1

66000/√3/0.1/√3

0.2

0.5

15

30

5-10/5

0.2S

0.5S

12.5

10-20/5

15-30/5

500-1000



Outline drawing:

Wiring Diagram:


Contact Us

Switchboard:+86-755-86000443

International Sales :+86-755-86000713+86-13823790397

Email:international2@chuangy.com

Add:Room 101 / 401, Building B, Jiada R&D Building, Songpingshan Road No.5, Songpingshan Community, Xili Street, Nanshan District, Shenzhen, China





Copyright © 2019. Shenzhen Chuangyin   Co., Ltd. All rights reserved. 粤ICP备11018302号