Model code:
Technical data:
|
No.
|
Technical data
|
data
|
Note
|
|
|
Range of current measurement
|
0.5 - 5000 A
|
(80 dBSignal range)
|
|
|
Output
|
0 - 5 A(RMS)
|
|
|
|
Variable range stalls
|
500A,1kA,2.5kA,5kA
|
(selectable )
|
|
|
Max burden
|
1.25 VA each channel
|
|
|
|
Max output
impedance
|
50 mΩ
|
|
|
|
Measuring channel
|
Single / three phase
|
|
|
|
frequency
|
50/60 Hz
|
|
|
|
Ratio error
|
±1%
|
|
|
|
Phrase error
|
< 1.5 ° @ 50Hz
|
|
|
|
Linearity
|
±0.3% (5% - 120%In)
|
|
|
|
Position sensitivity
|
±2%
|
|
|
|
Field effect
|
±1% Range (distance coil)>200mm)
|
|
|
|
environment
|
Indoor
|
|
|
|
Power requirements
|
voltage:48VDC ±10%,30w
|
|
|
current:0.6安培 DC @ 48VDC
|
|
|
|
Cable length
|
2m(Measuring head to electronic module)
|
|
|
|
output/input connection
|
18 - 28 AWG / 12 - 18 AWG
|
|
|
|
Operating temperature
|
-20℃-40℃
|
|
|
|
Relative humidity
|
5%〜95%no Condensation
|
|
|
|
Accessories
|
TS35/7 DIN installation trail
|
|
Note :All precision is specified at 20 ° C and the coil is centered on the conductor. Typical accuracy of the coil <1%。
Dimension and schematic:
The match coil can be our “CY-RCT01”or“CY-RCT02” series, or customized also.
Function and Application :
Function :General measurement and protection in power systems for highly mobile or space-constrained or uninterrupted power systems.
Application :Uses: power instrumentation, electronic multi-function energy meter and field calibrator, instrumentation measurement and protection.
Installation instruction:
Attention:
When flexible rogowski coil measurement probe connected, the cable under test should be placed in the middle of the flexible rogowski coil and the coil can be kept vertical to effectively reduce the measurement error.
in daily use , please ensure the correct connection of the XS1 terminal's positive and negative polarity of the power supply, once incorrect connection, the inside chip will be damaged.
If the output channel for more than 5 amps RMS may cause RōCoilTCA-5 to overheat and damage.